# High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline

In short. In-service double line-plug isolation above 2,000 psi on a sour dense-phase CO2 pipeline to retrieve a stuck pig and replace a leaking valve.

Source: T.D. Williamson. Account type: Vendor account.

During routine cleaning of a U.S. dense-phase CO2 pipeline that had run for more than 20 years at up to 2,400 psi, a pig became stuck and a nearby section valve was found leaking. The gas also contained about 1 percent H2S. The operator would not shut the line down and had to stay above 2,000 psi. Using equipment TDW had custom-built for this customer in 2005-2006, crews welded plugging tees in service, hot-tapped the line, and set a double line-plug isolation. TDW says the pig was then removed, the valve was replaced, and a tee and dead leg were cut out for straight pipe, all without a shutdown. The case is vendor-authored but is a rare public high-pressure CO2 hot-tap example.

## Method

In-service welding of line-plug split tees, hot tap through temporary sandwich valves, and a double line-plug isolation (with experience addressing H2S, rapid gas decompression, and weld cooling). After isolation, the stuck pig was removed, a leaking section valve was replaced, and an inline tee and dead leg were replaced with straight pipe.

## Defect

Stuck cleaning pig and a leaking section valve on a live dense-phase CO2 line containing about 1 percent H2S

## Pipe

Liquid-phase carbon dioxide at up to 2,400 psi (165 bar). Minimum intervention pressure was kept at 2,000 psi (138 bar). plugging heads were rated to 2,200 psi; sandwich valves were Class 900; split tees were 1,500-pound rated. United States. Pipe diameter not stated.

## Outcome

TDW reports a successful hot tap and double line-plug isolation while holding at least 2,000 psi, removal of the pig, valve replacement, and replacement of a tee and dead leg, without interrupting operation.

Schedule, cost, and service-life figures in this note are the publisher’s claims. They were not checked against an operator record or a laboratory report.

Dates: Custom Class 900 equipment was designed in 2005 and first used in 2006. The date of this later job is not stated.

Maker named in the source: T.D. Williamson. The source uses the vendor’s trademarked name STOPPLE® for its line-plugging equipment.