06 · Coatings and corrosion protection
Cased crossings and shielded corrosion
In short Why a steel casing under a road or railroad is a corrosion and assessment problem: isolation requirements in §192.467 and §195.575, casing design in §192.323, metallic and electrolytic contacts, PHMSA's cased-pipe ECDA guidelines, and repairs made inside or at the end of a casing.
A casing is a larger steel pipe around the carrier at a road or railroad crossing. It was meant to protect the carrier from load and to let it be replaced without digging up the road. It also creates a closed annulus where water can collect, a steel shell that blocks cathodic protection current, and a section of carrier that most above-ground surveys cannot see. Corrosion inside casings is a recognized integrity threat, and repairs made at casings have failed in public cases.
What the rules require
Casing design (gas). Section 192.323 applies to casings on transmission lines and mains under railroads and highways. The casing must withstand superimposed loads. If water can enter, the ends must be sealed. If an unvented casing is sealed with seals strong enough to hold MAOP, the casing must be designed to hold that pressure at no more than 72% of SMYS. Vents must be protected from weather so water cannot enter.
Isolation (gas). Section 192.467(c) requires each pipeline to be electrically isolated from metallic casings that are part of the underground system. If isolation is impractical, other measures must be taken to minimize corrosion of the pipeline inside the casing. Paragraph (d) requires inspection and electrical tests to show the isolation is adequate.
Isolation (liquid). Section 195.575 requires isolation from other metallic structures unless they are interconnected and protected as a single unit, and requires each isolation to be inspected and electrically tested. It has no casing-specific paragraph. A casing is one of the “other metallic structures.”
Two kinds of contact
Metallic short. The carrier touches the casing through failed spacers, settlement, or debris. CP current meant for the carrier flows to the bare casing instead. Pipe-to-soil readings at the test station converge with casing-to-soil readings. The carrier inside may then be unprotected wherever its coating is damaged.
Electrolytic contact. Water or mud fills the annulus and connects carrier and casing through an electrolyte. The casing shields the carrier from the CP system outside, so the carrier coating is all that protects the carrier. Electrolytic contact can be harder to confirm from the surface than a metallic short.
Both are why the regulation allows “other measures” only when isolation is impractical. Common measures include filling the annulus with a dielectric or corrosion-inhibiting material, removing the casing, and monitoring. AMPP publishes the industry practice for steel-cased pipelines. It is named here by reference only.
Assessing what is inside
In-line inspection reads the carrier wall inside a casing the same way it reads any other pipe. External corrosion direct assessment, which depends on above-ground surveys, is much harder. PHMSA’s cased-pipe guidelines (Revision 1, November 2010) supplement the NACE ECDA practice for gas transmission HCAs. They say cased pipe presents significant challenges at the region-identification, indirect-inspection, and direct-examination steps. Points from the guidelines:
- Data treated as critical include casing construction, fill material, casing monitoring data (shorted or not, fill condition), coating type and condition, and any history of metallic shorts or electrolytic contact.
- Operating pressure above 60% of SMYS and operating temperature above 120°F should be considered higher risk.
- The guidelines may not be used if the carrier pipe is bare.
- Direct examination options are limited. Cutting back the casing and inspecting visually as far in as possible with borescopes or cameras may help when the anomaly is near the casing ends.
- Where the guidelines cannot be implemented for a casing, PHMSA considers ECDA not feasible for that casing.
PHMSA also publishes FAQs on cased-pipe assessment, which state that they create no new requirements.
Repairs at casings
A repair at a casing end, or inside a cut-back casing, inherits the casing’s problems. The annulus can trap water against the repair. CP may not reach it. The next survey may not see it.
The public example is the Sterling Heights, Michigan release in September 2026, written up as a case study and an enforcement note. Crude leaked through two holes in the longitudinal weld of an uncoated Type B sleeve installed in 2010. The sleeve sat in a cut-out of a 20-inch concrete-coated casing, and oil ran along the sleeve and down the casing. The operator could not find the original repair records for that sleeve or for 11 others on the line.
For any repair at a casing, the job file should show:
- How the repaired pipe and the repair hardware will be coated, and that the coating was holiday-tested. See Coating at repair sites.
- Whether the casing was cut back, how the cut was closed or sealed, and whether the annulus was filled.
- Carrier-to-casing isolation tested after the work.
- The repair’s location recorded relative to the casing ends, so later ILI calls can be matched to it. PHMSA’s ADB-2026-02 on Type A sleeves describes the same mechanism (water in a tight annulus and shielded CP) and recommends a repair inventory.
Other shielding geometries
The casing is the most common shielded geometry, not the only one. Disbonded tape, insulation jackets, and rock shield can create the same conditions. PHMSA’s ADB-2016-04 followed the 2015 Line 901 rupture, where external corrosion developed under foam insulation with water in it despite CP readings that would normally be considered adequate. See Cathodic protection and Coating types.
Sources
- 49 CFR 192.323, casing — eCFR
- 49 CFR 192.467, electrical isolation — eCFR
- 49 CFR 195.575, electrical isolation — eCFR
- PHMSA, Guidelines for Integrity Assessment of Cased Pipe in Gas Transmission Pipelines in HCAs, Revision 1, November 2010 (PDF) — PHMSA
- PHMSA, FAQs on integrity assessment of cased pipe — PHMSA
- ADB-2016-04, corrosion under insulated coatings — Federal Register
- ADB-2026-02, integrity risks of Type A repair sleeves — Federal Register
- AMPP, publisher of NACE SP0502 and casing practice standards — AMPP
Related notes
- CPF 4-2026-025-CAO: Sterling Heights sleeve failure — Enforcement and incidents
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025) — Case studies
- Advisory bulletins that bear on repair — Regulations and official guidance
- In-ditch examination and ILI verification — Defect assessment
- Type A steel sleeves — Repair methods
- Lessons from public investigations — Regulations and official guidance
Also in Coatings and corrosion protection
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction