07 · Case studies
Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025)
In short Crude oil leak in 2026 from two holes in a 2010 Type B sleeve seam weld on the 16-inch Marysville-Toledo pipeline, leading to CAO 4-2026-025.
Source: PHMSA, Office of Pipeline Safety (2026). Account type: Independent regulatory record.
A member of the public reported crude oil seeping from the ground in Sterling Heights, Michigan, on 18 September 2026. After excavation, Energy Transfer confirmed the source was a Type B sleeve installed in 2010 on the 16-inch X52 Marysville-Toledo Crude Pipeline. Oil was leaking through two holes in the sleeve’s longitudinal weld, then traveling along an uncoated sleeve inside a 20-inch cased, concrete-coated crossing. The operator could not find the original repair records for that sleeve or for 11 other sleeves on the same line. PHMSA issued Corrective Action Order CPF 4-2026-025 and the company prepared to cut out the failed sleeve and install pretested pipe.
Method
Type B pressure-containing steel sleeve (failed in service). Operator planned to remove the failed sleeve and replace the pipe with pretested pipe (cut-out).
Defect
Failure of the repair itself: two holes in the longitudinal weld of the Type B sleeve. The original defect under the sleeve is unknown because installation records could not be located.
Pipe
Marysville-Toledo Crude (MTC) Pipeline, about 130 miles of 16-inch, 0.281-inch wall, Grade X52, coal-tar coated pipe, in a 20-inch steel casing with concrete coating at the failure site. Crude oil service. Operating pressure at the time of failure was not stated in the order.
Outcome
At least 15 barrels of crude oil were recovered from the site and a nearby storm drain, in a high-consequence area. The line was shut in. The sleeve, installed in 2010, was uncoated and sat in a cut-out of the casing; oil ran down the casing. Energy Transfer lacked original records for this sleeve and for 11 other sleeves on the MTC line, and PHMSA ordered a broader sleeve inventory and integrity plan, plus independent mechanical/metallurgical testing and a separate root-cause analysis.
This account is taken from a public regulatory or investigative record.
Dates: Release reported 18 September 2026; source confirmed 19 September 2026; Corrective Action Order issued 21 September 2026.
Maker named in the source: Sleeve manufacturer not named.
Sources
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025) — PHMSA, Office of Pipeline Safety
Related notes
- Type B steel sleeves — Repair methods
- In-service welding and hydrogen pipelines — Repair methods
- Burst test of a 24-inch leaking pipe with a Type B sleeve, 2019 — Test reports
- Type B sleeve fit-up, tight and loose, 2021 — Test reports
- Steel repair sleeve MAOP tables — Assessment
- Choosing a repair — Repair methods
Also in Case studies
- Type A sleeve leak on the Twin Oaks Pipeline, Upper Makefield Township, Pennsylvania
- Type A sleeve leak on Colonial Line 1, Huntersville, North Carolina (CPF 2-2021-005-NOPSO)
- Type A sleeve leak on Colonial Line, Gwinnett County (Harbins Road), Georgia
- Type A sleeve leak on the CNG/Plantation pipeline, Belton, South Carolina
- Type C compression-sleeve repairs on the Oasis Pipeline, Texas
- In-service X70 Type B sleeve installation on West-East Gas Pipeline Line 3, China
- Subsea Clamp+Sleeve repair of a buckled 10-inch crude line, South Marsh Island Block 59
- ROV-installed Flange Repair Split+Sleeve on a 10-inch water-injection line, offshore Angola
- ROV-installed leak-sealing clamp on a 10-inch water-injection riser flange, Foinaven field
- Emergency leak repair on a 30-inch onshore pipeline with a bolt-on fitting
- Composite sleeve repair of 900 feet of cooling-tower corrosion on a U.S. refinery pipeline
- Composite sleeve repair of a dent and seam-weld crack on a 24-inch crude-oil pipeline
- Underwater composite sleeve repair of girth-weld corrosion on a 12-inch gas pipeline
- Composite sleeve repair of a rockfall dent on a 36-inch hydroelectric pipeline in the French Alps
- Burst test of a composite sleeve repair recovered after 25 years in service (installed 1995)
- Composite pipe-wrap repairs of corrosion on Equistar Pipeline, Texas
- Weld-wrap composite reinforcement of an internal weld defect on a 24-inch products pipeline, Western Europe
- Composite repair of a 32-inch offshore riser, Thailand
- Splash-zone composite repair of mechanical damage on a 12-inch subsea crude line, Gulf of Mexico
- Carbon-fiber repair of a deep crack on a 900 mm gas-transmission bend
- Epoxy-filled sleeve encapsulation of a large dent on a 14-inch trunkline, Papua New Guinea
- High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline
- Line-plug train isolation and diversion of two 24-inch gas transmission lines under a planned Singapore subway station
- Line-plug train isolation to decommission a gas-processing plant off a 36-inch transmission line, Alabama
- Emergency double line-plug isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas
- 12-inch double line-plug isolation with bypass for a live gas-line repair, Oklahoma
- Line stop to connect 8-inch PE gas mains, St. Louis
- Insertion valves and line stops after a sheared 8-inch valve, Covington, Ohio
- Epoxy recoating of HDD-damaged girth and spiral welds, Kansas
- West Virginia 30-inch leak at a previous composite wrap
- Port Allen valve-station dent reinforced with an E-glass wrap
- 14-inch diesel line at Redding, Pennsylvania, carbon wrap
- Hinged protective tools on a 24-inch Florida line during bridge work
- Custom Type B sleeve around an existing clamp, Florida
- Type B sleeves replacing mechanical clamps at a Texas refinery
- Double-hump girth-weld sleeve on a 26-inch Kentucky gas line
- Compression sleeve on a crude line, Middle East operator
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction