Emergency double line-plug isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas
In short Emergency hot tap and double line-plug isolation to extinguish and isolate a burning 14-inch NGL pipeline after a third-party strike.
Source: T.D. Williamson (8 October 2020 media release) (2020). Account type: Vendor account.
In West Texas a third-party contractor hit a 14-inch NGL line, causing an explosion and a fire with flames reported at 300 feet. Four people were injured, one critically. The operator rerouted product at a much lower rate, and TDW mobilized a large hot-tap crew. Technicians performed a double line-plug isolation; sweeping the tap holes caused the fire to bellow until the heads were fully set, which then cut off the vapor feeding the fire. TDW says the isolation allowed the damaged section to be repaired without a full system shutdown. This is a company press release, not an accident investigation.
Method
Double line-plug hot-tap and plug isolation on a live, burning line, after product was rerouted at a reduced flow rate, so the damaged section could be isolated and repaired while the system stayed in service
Defect
Third-party excavation strike, rupture, and fire
Pipe
14-inch natural-gas-liquids pipeline, West Texas. Operating pressure at the time of the strike is not stated. Responding firefighters recorded temperatures above 1,500 F, and flames were described as 300 feet high.
Outcome
TDW reports that eight hot-tap technicians mobilized from several service centers, a double line-plug was set, and once the heads sealed they starved the fire of NGL vapors so it went out. The company says fittings left the shop in less than six hours and the field problem was solved in less than a day on site. A separate 2019 TDW PDF describes a similar 20-inch NGL trencher-strike fire; the two accounts differ in diameter and some details and should not be assumed to be the same job.
Schedule, cost, and service-life figures in this note are the publisher’s claims. They were not checked against an operator record or a laboratory report.
Dates: Press release dated 8 October 2020.
Maker named in the source: T.D. Williamson. The source uses the vendor’s trademarked name STOPPLE® for its line-plugging equipment.
Sources
- Emergency double STOPPLE® isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas — T.D. Williamson (8 October 2020 media release)
Related notes
- Hot tapping and line plugging — Repair methods
- In-service welding and hydrogen pipelines — Repair methods
- Cut-out and replacement — Repair methods
- ASME B31.8 and B31.8S — Codes and standards
- Part 192 repair and integrity duties — Regulations and official guidance
- Choosing a repair — Repair methods
Also in Case studies
- Type A sleeve leak on the Twin Oaks Pipeline, Upper Makefield Township, Pennsylvania
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025)
- Type A sleeve leak on Colonial Line 1, Huntersville, North Carolina (CPF 2-2021-005-NOPSO)
- Type A sleeve leak on Colonial Line, Gwinnett County (Harbins Road), Georgia
- Type A sleeve leak on the CNG/Plantation pipeline, Belton, South Carolina
- Type C compression-sleeve repairs on the Oasis Pipeline, Texas
- In-service X70 Type B sleeve installation on West-East Gas Pipeline Line 3, China
- Subsea Clamp+Sleeve repair of a buckled 10-inch crude line, South Marsh Island Block 59
- ROV-installed Flange Repair Split+Sleeve on a 10-inch water-injection line, offshore Angola
- ROV-installed leak-sealing clamp on a 10-inch water-injection riser flange, Foinaven field
- Emergency leak repair on a 30-inch onshore pipeline with a bolt-on fitting
- Composite sleeve repair of 900 feet of cooling-tower corrosion on a U.S. refinery pipeline
- Composite sleeve repair of a dent and seam-weld crack on a 24-inch crude-oil pipeline
- Underwater composite sleeve repair of girth-weld corrosion on a 12-inch gas pipeline
- Composite sleeve repair of a rockfall dent on a 36-inch hydroelectric pipeline in the French Alps
- Burst test of a composite sleeve repair recovered after 25 years in service (installed 1995)
- Composite pipe-wrap repairs of corrosion on Equistar Pipeline, Texas
- Weld-wrap composite reinforcement of an internal weld defect on a 24-inch products pipeline, Western Europe
- Composite repair of a 32-inch offshore riser, Thailand
- Splash-zone composite repair of mechanical damage on a 12-inch subsea crude line, Gulf of Mexico
- Carbon-fiber repair of a deep crack on a 900 mm gas-transmission bend
- Epoxy-filled sleeve encapsulation of a large dent on a 14-inch trunkline, Papua New Guinea
- High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline
- Line-plug train isolation and diversion of two 24-inch gas transmission lines under a planned Singapore subway station
- Line-plug train isolation to decommission a gas-processing plant off a 36-inch transmission line, Alabama
- 12-inch double line-plug isolation with bypass for a live gas-line repair, Oklahoma
- Line stop to connect 8-inch PE gas mains, St. Louis
- Insertion valves and line stops after a sheared 8-inch valve, Covington, Ohio
- Epoxy recoating of HDD-damaged girth and spiral welds, Kansas
- West Virginia 30-inch leak at a previous composite wrap
- Port Allen valve-station dent reinforced with an E-glass wrap
- 14-inch diesel line at Redding, Pennsylvania, carbon wrap
- Hinged protective tools on a 24-inch Florida line during bridge work
- Custom Type B sleeve around an existing clamp, Florida
- Type B sleeves replacing mechanical clamps at a Texas refinery
- Double-hump girth-weld sleeve on a 26-inch Kentucky gas line
- Compression sleeve on a crude line, Middle East operator
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction