07 · Case studies
High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline
In short In-service double line-plug isolation above 2,000 psi on a sour dense-phase CO2 pipeline to retrieve a stuck pig and replace a leaking valve.
Source: T.D. Williamson. Account type: Vendor account.
During routine cleaning of a U.S. dense-phase CO2 pipeline that had run for more than 20 years at up to 2,400 psi, a pig became stuck and a nearby section valve was found leaking. The gas also contained about 1 percent H2S. The operator would not shut the line down and had to stay above 2,000 psi. Using equipment TDW had custom-built for this customer in 2005-2006, crews welded plugging tees in service, hot-tapped the line, and set a double line-plug isolation. TDW says the pig was then removed, the valve was replaced, and a tee and dead leg were cut out for straight pipe, all without a shutdown. The case is vendor-authored but is a rare public high-pressure CO2 hot-tap example.
Method
In-service welding of line-plug split tees, hot tap through temporary sandwich valves, and a double line-plug isolation (with experience addressing H2S, rapid gas decompression, and weld cooling). After isolation, the stuck pig was removed, a leaking section valve was replaced, and an inline tee and dead leg were replaced with straight pipe.
Defect
Stuck cleaning pig and a leaking section valve on a live dense-phase CO2 line containing about 1 percent H2S
Pipe
Liquid-phase carbon dioxide at up to 2,400 psi (165 bar). Minimum intervention pressure was kept at 2,000 psi (138 bar). plugging heads were rated to 2,200 psi; sandwich valves were Class 900; split tees were 1,500-pound rated. United States. Pipe diameter not stated.
Outcome
TDW reports a successful hot tap and double line-plug isolation while holding at least 2,000 psi, removal of the pig, valve replacement, and replacement of a tee and dead leg, without interrupting operation.
Schedule, cost, and service-life figures in this note are the publisher’s claims. They were not checked against an operator record or a laboratory report.
Dates: Custom Class 900 equipment was designed in 2005 and first used in 2006. The date of this later job is not stated.
Maker named in the source: T.D. Williamson. The source uses the vendor’s trademarked name STOPPLE® for its line-plugging equipment.
Sources
Related notes
- Hot tapping and line plugging — Repair methods
- In-service welding and hydrogen pipelines — Repair methods
- Cut-out and replacement — Repair methods
- ASME B31.8 and B31.8S — Codes and standards
- Part 192 repair and integrity duties — Regulations and official guidance
- Choosing a repair — Repair methods
Also in Case studies
- Type A sleeve leak on the Twin Oaks Pipeline, Upper Makefield Township, Pennsylvania
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025)
- Type A sleeve leak on Colonial Line 1, Huntersville, North Carolina (CPF 2-2021-005-NOPSO)
- Type A sleeve leak on Colonial Line, Gwinnett County (Harbins Road), Georgia
- Type A sleeve leak on the CNG/Plantation pipeline, Belton, South Carolina
- Type C compression-sleeve repairs on the Oasis Pipeline, Texas
- In-service X70 Type B sleeve installation on West-East Gas Pipeline Line 3, China
- Subsea Clamp+Sleeve repair of a buckled 10-inch crude line, South Marsh Island Block 59
- ROV-installed Flange Repair Split+Sleeve on a 10-inch water-injection line, offshore Angola
- ROV-installed leak-sealing clamp on a 10-inch water-injection riser flange, Foinaven field
- Emergency leak repair on a 30-inch onshore pipeline with a bolt-on fitting
- Composite sleeve repair of 900 feet of cooling-tower corrosion on a U.S. refinery pipeline
- Composite sleeve repair of a dent and seam-weld crack on a 24-inch crude-oil pipeline
- Underwater composite sleeve repair of girth-weld corrosion on a 12-inch gas pipeline
- Composite sleeve repair of a rockfall dent on a 36-inch hydroelectric pipeline in the French Alps
- Burst test of a composite sleeve repair recovered after 25 years in service (installed 1995)
- Composite pipe-wrap repairs of corrosion on Equistar Pipeline, Texas
- Weld-wrap composite reinforcement of an internal weld defect on a 24-inch products pipeline, Western Europe
- Composite repair of a 32-inch offshore riser, Thailand
- Splash-zone composite repair of mechanical damage on a 12-inch subsea crude line, Gulf of Mexico
- Carbon-fiber repair of a deep crack on a 900 mm gas-transmission bend
- Epoxy-filled sleeve encapsulation of a large dent on a 14-inch trunkline, Papua New Guinea
- Line-plug train isolation and diversion of two 24-inch gas transmission lines under a planned Singapore subway station
- Line-plug train isolation to decommission a gas-processing plant off a 36-inch transmission line, Alabama
- Emergency double line-plug isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas
- 12-inch double line-plug isolation with bypass for a live gas-line repair, Oklahoma
- Line stop to connect 8-inch PE gas mains, St. Louis
- Insertion valves and line stops after a sheared 8-inch valve, Covington, Ohio
- Epoxy recoating of HDD-damaged girth and spiral welds, Kansas
- West Virginia 30-inch leak at a previous composite wrap
- Port Allen valve-station dent reinforced with an E-glass wrap
- 14-inch diesel line at Redding, Pennsylvania, carbon wrap
- Hinged protective tools on a 24-inch Florida line during bridge work
- Custom Type B sleeve around an existing clamp, Florida
- Type B sleeves replacing mechanical clamps at a Texas refinery
- Double-hump girth-weld sleeve on a 26-inch Kentucky gas line
- Compression sleeve on a crude line, Middle East operator
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction