Composite repair of a 32-inch offshore riser, Thailand
In short Composite and subsea-epoxy reinforcement of severe wall loss on a 32-inch offshore gas riser in Thailand, avoiding a prolonged shutdown.
Source: Offshore magazine (1 October 2010), article by Matt Green, Neptune Research Inc. (2010). Account type: Trade press.
An offshore operator in Thailand faced severe wall loss on a 32-inch riser that fed power-plant fuel supply. A cut-out would have required a long shutdown. The pipe was blasted, pits were filled with epoxy putty, a Kevlar-reinforced subsea epoxy was applied, and about 10 feet of subsea composite wrap was installed. The manufacturer reported the work took less than 36 hours, a four-hour test at 1,700 psi was successful, and the riser went back to its 1,580 psi design pressure and the field’s 630 MMcf/d rate the same afternoon. The article also notes Petrobras diver applications of the same system to 100 metres, but those jobs are described only in general terms.
Method
NRI Syntho-Glass XT water-activated fiberglass composite wrap over high-compression epoxy putty and Syntho-SubSea LV epoxy, applied over about 10 feet (3 m)
Defect
Severe wall loss on an offshore riser, to the point that the alternative was a full cut-out and replacement
Pipe
32-inch riser on an offshore oil facility in Thailand supplying fuel to power plants. Restored to the original design pressure of 1,580 psi (109 bar). A four-hour pressure test was run at 1,700 psi (117 bar). The field is described as producing 630 MMcf/d.
Outcome
The author reports the repair was completed in less than 36 hours, passed the 1,700 psi test, and the pipe returned to full operation the same afternoon, avoiding a shutdown the operator had valued at about $125,000 per hour. Those time and cost figures are from the product manufacturer.
This account is taken from a public regulatory or investigative record.
Dates: Article dated 1 October 2010; the repair was at or shortly before that date.
Maker named in the source: Neptune Research Inc. (NRI), later part of CSNRI.
Sources
- Syntho-Glass XT repair of a 32-inch offshore riser, Thailand — Offshore magazine (1 October 2010), article by Matt Green, Neptune Research Inc.
Related notes
- Composite wraps — Repair methods
- ASME PCC-2 — Codes and standards
- ISO 24817 — Codes and standards
- Corrosion metal loss — Defect assessment
- AB-539: engineered composite alterations in Alberta — Regulations and official guidance
- Choosing a repair — Repair methods
Also in Case studies
- Type A sleeve leak on the Twin Oaks Pipeline, Upper Makefield Township, Pennsylvania
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025)
- Type A sleeve leak on Colonial Line 1, Huntersville, North Carolina (CPF 2-2021-005-NOPSO)
- Type A sleeve leak on Colonial Line, Gwinnett County (Harbins Road), Georgia
- Type A sleeve leak on the CNG/Plantation pipeline, Belton, South Carolina
- Type C compression-sleeve repairs on the Oasis Pipeline, Texas
- In-service X70 Type B sleeve installation on West-East Gas Pipeline Line 3, China
- Subsea Clamp+Sleeve repair of a buckled 10-inch crude line, South Marsh Island Block 59
- ROV-installed Flange Repair Split+Sleeve on a 10-inch water-injection line, offshore Angola
- ROV-installed leak-sealing clamp on a 10-inch water-injection riser flange, Foinaven field
- Emergency leak repair on a 30-inch onshore pipeline with a bolt-on fitting
- Composite sleeve repair of 900 feet of cooling-tower corrosion on a U.S. refinery pipeline
- Composite sleeve repair of a dent and seam-weld crack on a 24-inch crude-oil pipeline
- Underwater composite sleeve repair of girth-weld corrosion on a 12-inch gas pipeline
- Composite sleeve repair of a rockfall dent on a 36-inch hydroelectric pipeline in the French Alps
- Burst test of a composite sleeve repair recovered after 25 years in service (installed 1995)
- Composite pipe-wrap repairs of corrosion on Equistar Pipeline, Texas
- Weld-wrap composite reinforcement of an internal weld defect on a 24-inch products pipeline, Western Europe
- Splash-zone composite repair of mechanical damage on a 12-inch subsea crude line, Gulf of Mexico
- Carbon-fiber repair of a deep crack on a 900 mm gas-transmission bend
- Epoxy-filled sleeve encapsulation of a large dent on a 14-inch trunkline, Papua New Guinea
- High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline
- Line-plug train isolation and diversion of two 24-inch gas transmission lines under a planned Singapore subway station
- Line-plug train isolation to decommission a gas-processing plant off a 36-inch transmission line, Alabama
- Emergency double line-plug isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas
- 12-inch double line-plug isolation with bypass for a live gas-line repair, Oklahoma
- Line stop to connect 8-inch PE gas mains, St. Louis
- Insertion valves and line stops after a sheared 8-inch valve, Covington, Ohio
- Epoxy recoating of HDD-damaged girth and spiral welds, Kansas
- West Virginia 30-inch leak at a previous composite wrap
- Port Allen valve-station dent reinforced with an E-glass wrap
- 14-inch diesel line at Redding, Pennsylvania, carbon wrap
- Hinged protective tools on a 24-inch Florida line during bridge work
- Custom Type B sleeve around an existing clamp, Florida
- Type B sleeves replacing mechanical clamps at a Texas refinery
- Double-hump girth-weld sleeve on a 26-inch Kentucky gas line
- Compression sleeve on a crude line, Middle East operator
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction