07 · Case studies
Subsea isolation and permanent bypass after anchor damage on an 8-inch condensate line, Gulf of Thailand
In short Divers installed mechanical hot-tap clamps on a live 8-inch gas-condensate line at 60 m water depth, hot-tapped it, set a dual-seal isolation, and commissioned a permanent seabed bypass around pipe dragged by an anchor.
Source: STATS Group. Account type: Vendor account.
A section of an 8-inch gas-condensate export pipeline in the Gulf of Thailand had been dragged about 8 metres from its original position by a vessel anchor and needed a permanent repair. The line was live, in about 60 metres of water, at pressures the vendor gives as 7 to 21 bar. The operator and the installation contractor, CUEL Ltd, required the damaged pipe to be isolated and removed without shutting in production and without putting divers on an unisolated line.
The vendor’s account, completed in December 2016, is as follows. Six permanent 8-inch mechanical hot-tap clamps with 8-inch branched offtakes were installed by saturation divers at three locations. At each location one clamp was the tie-in for a new bypass and the other was the entry for a dual-seal isolation tool. After the clamps were bolted up, the annulus and body flange were pressure-tested at 56 bar. A hot-tap machine then cut the coupon from the pressurised pipe; the coupon was recovered, inspected, and measured. An 8-inch bypass spool was installed on the seabed and the clamp valves were opened so flow could enter the bypass as well as the original line.
Isolation tools with primary and secondary seals were then deployed through full-bore hot-tap openings in the clamps, set hydraulically from the vessel, and seal-tested to a double-block-and-bleed isolation. The vendor says an isolation certificate was issued and renewed every 12 hours. The isolated damaged section was flushed back into the export line, depressurised to the subsea ambient pressure of 6 bar, and cut with diamond-wire cutters. Abandonment plugs were set in the open ends of the damaged pipe for wet storage. Permanent mechanical connectors with blind flanges were fitted to the remaining pipe ends and annulus-tested at 56 bar. The isolation tools were then unset and recovered, completion plugs were set in the clamp flanges and pressure-tested, the slab valves were removed, and blind flanges were installed as a second barrier.
The onshore programme included a representative test on actual pipe sections and training of the vessel dive team on the subsea hot-tap machine before the six offshore taps.
Schedule, cost, and service-life figures in this note are the publisher’s claims. They were not checked against an operator record or a laboratory report.
Dates: The vendor states the repair was completed in December 2016.
Maker named in the source: STATS Group. The source uses the vendor’s trademarked name BISEP for the dual-seal isolation tool deployed through a single hot-tap opening.
Sources
- 8" Subsea Pipeline Isolation & Repair, Gulf of Thailand — STATS Group
Related notes
- Hot tapping and line plugging — Repair methods
- In-service welding and hydrogen pipelines — Repair methods
- Cut-out and replacement — Repair methods
- ASME B31.8 and B31.8S — Codes and standards
- Part 192 repair and integrity duties — Regulations and official guidance
- Choosing a repair — Repair methods
Also in Case studies
- Type A sleeve leak on the Twin Oaks Pipeline, Upper Makefield Township, Pennsylvania
- Type B sleeve leak on the Marysville-Toledo Crude Pipeline, Sterling Heights, Michigan (CAO 4-2026-025)
- Type A sleeve leak on Colonial Line 1, Huntersville, North Carolina (CPF 2-2021-005-NOPSO)
- Type A sleeve leak on Colonial Line, Gwinnett County (Harbins Road), Georgia
- Type A sleeve leak on the CNG/Plantation pipeline, Belton, South Carolina
- Type C compression-sleeve repairs on the Oasis Pipeline, Texas
- In-service X70 Type B sleeve installation on West-East Gas Pipeline Line 3, China
- Subsea Clamp+Sleeve repair of a buckled 10-inch crude line, South Marsh Island Block 59
- ROV-installed Flange Repair Split+Sleeve on a 10-inch water-injection line, offshore Angola
- ROV-installed leak-sealing clamp on a 10-inch water-injection riser flange, Foinaven field
- Emergency leak repair on a 30-inch onshore pipeline with a bolt-on fitting
- Composite sleeve repair of 900 feet of cooling-tower corrosion on a U.S. refinery pipeline
- Composite sleeve repair of a dent and seam-weld crack on a 24-inch crude-oil pipeline
- Underwater composite sleeve repair of girth-weld corrosion on a 12-inch gas pipeline
- Composite sleeve repair of a rockfall dent on a 36-inch hydroelectric pipeline in the French Alps
- Burst test of a composite sleeve repair recovered after 25 years in service (installed 1995)
- Composite pipe-wrap repairs of corrosion on Equistar Pipeline, Texas
- Weld-wrap composite reinforcement of an internal weld defect on a 24-inch products pipeline, Western Europe
- Composite repair of a 32-inch offshore riser, Thailand
- Splash-zone composite repair of mechanical damage on a 12-inch subsea crude line, Gulf of Mexico
- Carbon-fiber repair of a deep crack on a 900 mm gas-transmission bend
- Epoxy-filled sleeve encapsulation of a large dent on a 14-inch trunkline, Papua New Guinea
- High-pressure line-plug isolation to remove a stuck pig and replace a leaking valve on a CO2 pipeline
- Line-plug train isolation and diversion of two 24-inch gas transmission lines under a planned Singapore subway station
- Line-plug train isolation to decommission a gas-processing plant off a 36-inch transmission line, Alabama
- Emergency double line-plug isolation of a burning 14-inch NGL pipeline after a third-party strike, West Texas
- 12-inch double line-plug isolation with bypass for a live gas-line repair, Oklahoma
- Line stop to connect 8-inch PE gas mains, St. Louis
- Insertion valves and line stops after a sheared 8-inch valve, Covington, Ohio
- Epoxy recoating of HDD-damaged girth and spiral welds, Kansas
- West Virginia 30-inch leak at a previous composite repair
- Port Allen valve-station dent reinforced with an E-glass composite repair
- 14-inch diesel line at Redding, Pennsylvania, carbon-fiber composite repair
- Hinged protective tools on a 24-inch Florida line during bridge work
- Custom Type B sleeve around an existing clamp, Florida
- Type B sleeves replacing mechanical clamps at a Texas refinery
- Double-hump girth-weld sleeve on a 26-inch Kentucky gas line
- Compression sleeve on a crude line, Middle East operator
- High-pressure CO2 mid-line isolation and bypass for piggability upgrades, Cortez Pipeline
Spotted an error? Engineers keep this site honest.Report an error or suggest a correction